EVO S -
Installation and Servicing
Diagram: VF2
page 4 / 6
Line No. Value
Boiler pump supplied by the customer (all-or-nothing control)
Configure the extension module function
Function extension module 1
(6020)
Multifunctional
Configure the output to control the boiler
pump
Relay output QX23 module 1
(6032)
Boiler pump Q1
• Heating circuit 1
menu
Adjust the comfort setting
Comfort setpoint
(710)
- - -
Adjust the curve slope
Heating curve slope
(720)
- - -
Adjust the min. flow temperature if
necessary
Flow temp setpoint min
(740)
60°C (adjust
according to the
lower limit)
•
Switch the heating regime to permanent comfort
•
Domestic hot water
menu
Adjust the comfort setting
Nominal setpoint
(1610)
- - -
• Activate the DHW mode
• Configuration
menu
Save the sensors
Save sensors
(6200)
Yes (switches back
to no automatically)
F. ELECTRICAL AND HYDRAULIC VALIDATION
•
Inputs/outputs test
menu
Check the outputs
Alarm relay
Relay test
(7700)
Relay output QX1
DHW pump Q3
Relay test
(7700)
Relay output QX2
Direct circuit pump Q2
Relay test
(7700)
Relay output QX3
Boiler pump control, if supplied by
customer
Relay test
(7700)
Relay output QX23
module 1
Reset the outputs
Relay test
(7700)
No test
Check the sensor values
External sensor B9
Outside temp B9
(7730)
in °C
DHW sensor B3
DHW temp B3/B38
(7750)
in °C