27.08.2018
93 / 136
EVO S -
Installation and Servicing
If the boiler room's regulator is configured as slave clock, it must retrieve
the date and time.
In both cases
Line No.
Value
•
Configuration
menu
Check the hydraulic diagram
Check no. heat source 1
(6212)
14
Check no. heat source 2
(6213)
0
Check no. storage tank
(6215)
0
Check no. heating circuits
(6217) 0
•
Inputs/outputs test
menu
Check the outputs
Alarm relay
Relay test
(7700)
Relay output QX1
Boiler pump control, if supplied by customer
Relay test
(7700)
Relay output QX3
Reset the outputs
Relay test
(7700)
No test
Check the sensor values
Cascade cylinder outlet sensor B10
Sensor temp BX2
(7821)
in °C
On boiler No. 2 or the following boiler(s): slave
•
Inputs/outputs test
menu
Boiler pump control, if supplied by customer
Relay test
(7700)
Relay output QX3
Reset the outputs
Relay test
(7700)
No test
•
Configuration
menu
Check the hydraulic diagram
Check no. heat source 1
(6212)
14
Check no. heat source 2
(6213)
0
Check no. storage tank
(6215)
0
Check no. heating circuits
(6217)
0
Diagram : VF10
page 6 / 7