Installation and Servicing
4.7.7.
Connection of the AGU 2.550 module(s) (optional accessory)
To install the AGU 2.550 module(s), please refer to the manual provided with
the accessory.
4.7.8.
Fuses
The EVO S boiler is fitted with four fuses on the boiler controller (refer to the
label on the protective cover for their positions and characteristics).
Three spare fuses are also provided on the boiler controller.
4.7.5.
Connection of the boiler circulation pump (compulsory accessory)
4.7.5.1.
Accessory supplied by IDEAL
If the accessory is supplied by IDEAL, please refer to the installation manual
for the connection of the boiler circulation pump.
4.7.5.2.
Accessory supplied by the customer
The circulation pump is controlled by a 230 VAC (1A max.) output on the
NAVISTEM B3000 panel.
This output is active when a request for heat is in progress on the boiler.
If the circulation pump does not have a control switch:
Directly wire the power supply of the circulation pump (230 VAC - 1A
max.) to the terminal QX3 (contacts L3, N and ) on the NAVISTEM
B3000 panel. If the circulation pump consumes more than 1A, the power
supply must be relayed.
If the circulation pump is equipped with a dry-contact On / Off control:
Connect the power supply of the circulation pump directly from your
electric panel.
Use the QX3 output (contacts L3 and N) on the NAVISTEM B3000 panel
(230 VAC - 1 A max.) to wire the circulation pump relay control.
If the circulation pump is equipped with a dry-contact On / Off control:
Connect the power supply of the circulation pump directly from your
electric panel.
Use the UX2 or UX3 output on the NAVISTEM B3000 panel to wire the
circulation pump 0-10V control.
4.7.6.
Connection of the OCI 345 module (optional accessory)
To install the OCI 345 module, please refer to the manual provided with the
accessory.