27.08.2018
87 / 136
EVO S -
Installation and Servicing
Line No. Value
Check the sensor values
B3 DHW sensor
DHW temp B3/B38
(7750)
in °C
• Configuration
menu
Check the hydraulic diagram
Check no. heat source 1
(6212)
13
Check no. heat source 2
(6213)
0
Check no. storage tank
(6215)
4
Check no. heating circuits
(6217)
0
G. CONFIGURATION OPTIMISATION
DHW optimisation:
•
DHW tank
menu
Adjust the over value
Flow setpoint boost
(5020)
16 °C
Maintenance optimisation
A maintenance message may be generated that does not set the boiler to fault. This maintenance
message may be displayed after the following 3 counters have expired:
•
Time since last maintenance (or commissioning): set parameter 7044 to 12 months.
•
Operating hours of the burner (parameter 7040).
•
Number of starts (parameter 7042)
These last 2 parameters are dependent on the boiler's hydraulic installation. We recommend
using at least parameter 7044 for annual maintenance.
Diagram: VF24
page 4 / 4