Ethernet I/O Modules
2.2.2.3
tET-P2C2/tPET-P2C2/tET-P2A2/tPET-P2A2
Models
tET-P2C2
tPET-P2C2
tET-P2A2
tPET-P2A2
Digital Input
Input Channels
2
Input Type (Device)
Wet Contact (Sink, Source)
On Voltage Level
+10 V
DC
~ +50 V
DC
Off Voltage Level
+4 V
DC
Max.
Input Impedance
10 k
Ω
Counters
Max. Count: 4,294,967,285 (32 bits)
Min. Pulse Width: 0.15 ms
Frequency Measurement
3.5 kHz (without filter)
Overvoltage Protection
+70 V
DC
Isolation
3750 V
rms
Digital Output
Output Channels
2
Output Type (Module)
Sink, Open Collector (NPN)
Source, Open Collector (PNP)
Output Voltage
+5 V
DC
~ +30 V
DC
+10 V
DC
~ +40 V
DC
Max. Load Current
100 mA/channel
650 mA/channel
PWM
100 Hz Max. (The High/Low duty cycle R
ange = 5 ~ 65,535 ms)
Over-Voltage
+60 V
DC
+48 V
DC
Short Circuit Protection
-
Yes
Output Isolation
3750 V
rms
ICP DAS CO., LTD.