Ethernet I/O Modules
2.2.2.5
tET-P2R2/tPET-P2R2/tET-PD2R1/tPET-PD2R1
Models
tET-P2R2
tPET-P2R2
tET-PD2R1
tPET-PD2R1
Digital Input
Input Channels
2
Input Type (Device)
Wet Contact (Sink, Source)
Dry Contact (Source)
On Voltage Level
+10 V
DC
~ +50 V
DC
Close to GND
Off Voltage Level
+4 V
DC
Max.
Open
Input Impedance
10 k
Ω
-
Counters
Max. Count
4,294,967,285 (32 bits)
Min. Pulse Width
0.15 ms
Frequency Measurement
3.5 kHz (without filter)
Overvoltage Protection
+70 V
DC
-
Isolation
3750 V
rms
Effective Distance
-
500 M Max.
Relay Output
Output Channels
2
1
Output Type (Module)
Power Relay, Form A (SPST N.O.)
Output Voltage Range
250 V
AC
/30 V
DC
Max. Load Current
5.0 A/channel
Operate Time
6 ms
Release Time
3 ms
PWM
50 Hz max. (The
High/Low duty cycle range = 10 ~ 65,535 ms)
Electrical Life
(Resistive load)
VED
5 A 250 V
AC
30,000 ops (10 ops/minute) at 75 °C
5 A 30 V
DC
70,000 ops (10 ops/minute) at 75 °C
UL
5 A 250 V
AC/
30 V
DC
6,000 ops
3 A 250 V
AC/
30 V
DC
100,000 ops
Mechanical Life
20,000,000 ops. At no load (300 ops./ minute)
Output Isolation
3000 V
rms
Because of the characteristics of the relay functions, it is recommended that the PWM on
t(P)ET-P(D)2POR2/ t(P)ET-P2R2/ t(P)ET-PD2R1/ PETL-7060 series modules (i.e., modules with
relay functions) is not used for extended periods of time.
ICP DAS CO., LTD.
PETL/tET/tPET DIO Series User Manual, Ver. 2.1, Sep. 2014, Page: 23