3. With a small (1/8" or 3 mm) flat screwdriver, open the inlet gas supply pressure test port
by turning its center-screw one full turn counterclockwise.
4. Attach a manometer to the inlet pressure test port and turn on gas to appliance.
Static manometer reading should be ideally 7" w.c. for Natural Gas and 11" w.c.
for Propane.
Minimum and maximum static pressure should be between 4" and 14" w.c.
Monitor pressure throughout the commissioning (start-up) procedure. Pressure
may drop up to 1" to 2" w.c. at high fire.
5. To run the boiler at high fire, you can set the heat-out value in Test Operation mode to
the maximum MBH for the boiler. To do this, on the controller, go to
(More) >
Test
Operation
> In the
Fan Test: Heat Out
field, tap
0 MBtu
, then enter the maximum
MBH.
When the boiler reaches high fire, insert the combustion analyzer test probe into the
flue gas test port. Then verify that the CO
2
reading is within the combustion test targets
at
values.
6. Adjust the high fire according to values in
using the high fire adjustment screw
. Make tiny adjustments (may require several turns). Turning the High Fire screw
clockwise will lean out the flame.
7. Set the heat-out value in Test Operation mode to the minimum MBH for the boiler. To
do this, go to
(More) >
Test Operation
> In the
Fan Test: Heat Out
field, tap
0
MBtu
, then enter the minimum MBH.
8. Adjust the low fire according to values in
using the low fire adjustment screw.
Turn the screwdriver clockwise to raise the CO
2
% (to richen). Turn counter-clockwise to
lower CO
2
%. Start with ⅛ of a turn until you see the analyzer measure a change then
only make 1/16 adjustments. If changing direction on this adjustment, you may notice a
significant backlash.
9. Check the results and confirm the correct settings when you return the boiler to high
fire, and then to low fire.
Note
Clock the gas meter to confirm full maximum rating plate input.
10. To exit the
Test Operation
screen, select
Back
.
11. Remove the call for heat.
12. If a manometer is connected to the gas valve inlet gas pressure port:
a. Turn off the gas supply at the external gas shut-off valve.
b. Disconnect the manometer.
c. Tighten the inlet pressure port screw with a Torx 15 screwdriver.
13. Remove the analyzer probe, and install the test port plug.
72
Section: Boiler operation
Summary of Contents for SL 10-85 G3
Page 8: ...Intentionally left empty ...
Page 14: ...Intentionally left empty ...
Page 66: ...Figure 49 Electric wiring connections 62 Section Installation ...
Page 78: ...Intentionally left empty ...
Page 92: ...Intentionally left empty ...
Page 106: ...Internal wiring diagram Figure 53 Internal wiring diagram 102 Section Appendices ...
Page 107: ...Sequence of Operation Figure 54 Sequence of Operation 103 Sequence of Operation ...
Page 109: ...105 Exploded views of boiler parts ...
Page 114: ...110 Section Appendices ...
Page 122: ...Intentionally left empty ...