8.3.2 Temperature issues
Temperature issues
Issue
Diagnosis
Fix
Low heat
Operating temperature too low.
Increase temperature target.
Increase temperature target.
Priority parameters or load
configuration improperly set up.
Review load configuration parameters.
Appliance undersized.
Refer to Load Calculation vs. Boiler
Output.
Air trapped within system.
Bleed system as required.
Improper system piping.
Refer to recommended piping guidelines
for the respective boiler model.
System pump undersized.
Check pump manufacturer’s data/check
temp differential across heat exchanger.
Poor gas:air mixing.
Check CO
2
level.
Defective thermostat.
Refer to manufacturer’s instructions.
Obstruction in condensate
drain.
Inspect and clean condensate drain.
Appliance cycling on operating/
safety controls.
Check operation with
Ohmmeter/Voltmeter.
System radiation undersized.
Check manufacturer’s rating tables for
capacity per foot.
Temperature
exceeds thermostat
setting
Incorrect anticipator setting.
Check with Ammeter.
Thermostat not level.
Check level.
One or more zones
do not heat properly
Air trapped within zone(s)
piping
Vent system/zone as required.
Low radiation/ excessive heat
loss.
Check actual length of pipe using radiation
/ heat loss calculation.
Low flow rate to zone(s).
Check temperature drop across zone.
Defective zone valve/ zone
circulator.
Check operation per manufacturer’s
instructions.
97
8.3.2 Temperature issues
Summary of Contents for SL 10-85 G3
Page 8: ...Intentionally left empty ...
Page 14: ...Intentionally left empty ...
Page 66: ...Figure 49 Electric wiring connections 62 Section Installation ...
Page 78: ...Intentionally left empty ...
Page 92: ...Intentionally left empty ...
Page 106: ...Internal wiring diagram Figure 53 Internal wiring diagram 102 Section Appendices ...
Page 107: ...Sequence of Operation Figure 54 Sequence of Operation 103 Sequence of Operation ...
Page 109: ...105 Exploded views of boiler parts ...
Page 114: ...110 Section Appendices ...
Page 122: ...Intentionally left empty ...