3. Use a separate transformer – the 40 VA appliance inside the wiring box is for internal
systems only.
4. Wire individual load/zone valves to their associated contacts on the secondary pump/zone
valve connector. Do not confuse such “load/zone valves” with similar valves used to
segregate a single load type (e.g., those used on a zoned radiant floor) – see the next
section.
3.13.5 Thermostat / sensor wiring
Each of the four loads has dry contacts for thermostats as marked on the lower connector strip
(e.g., "Therm 1"). Gang lines from a multiple-zoned load (e.g., off the end-switches for each radiant
floor zone) present a common thermostat signal to the controller. Ensure that there are no
disturbing influences on the call-for-heat lines - for example, that there are no coils to switch an air
handler motor. Most power stealing thermostats can be connected directly to the Therm terminals.
Consult the
Controller
manual for more detailed instructions.
3.13.6 Thermostat heat anticipator
IBC “Therm” contacts draw no power, so an anticipator setting for the thermostat is not applicable
with these appliances. In the case of a single temperature / heat load where zone valves are used
to manage individual thermostatically controlled zones, each room thermostat’s heat anticipator
should be adjusted to the current draw of its associated zone valve.
61
3.13.5 Thermostat / sensor wiring
Summary of Contents for SL 10-85 G3
Page 8: ...Intentionally left empty ...
Page 14: ...Intentionally left empty ...
Page 66: ...Figure 49 Electric wiring connections 62 Section Installation ...
Page 78: ...Intentionally left empty ...
Page 92: ...Intentionally left empty ...
Page 106: ...Internal wiring diagram Figure 53 Internal wiring diagram 102 Section Appendices ...
Page 107: ...Sequence of Operation Figure 54 Sequence of Operation 103 Sequence of Operation ...
Page 109: ...105 Exploded views of boiler parts ...
Page 114: ...110 Section Appendices ...
Page 122: ...Intentionally left empty ...