Exhaust vent material – U.S.A
PVC, CPVC, or PPs venting materials are approved for use with these boilers in most of the
USA. Check local codes to determine if any materials are prohibited. The vent temperature is
limited with the use of the flue temperature sensor and software to ensure that the maximum
temperature of the PVC venting material is not exceeded. PVC venting material shall be
certified to Sch. 40 ASTM D1785 or D2665. CPVC material shall be certified to Sch. 40/ASTM
F441.
Exhaust vent material - general
Use of cellular core PVC (ASTM F891), cellular core CPVC, or Radel® (polyphenolsulfone) in
venting systems is prohibited. Do not use ABS or any cellular core pipe for exhaust venting.
3.7.4 Direct vent
Direct vent is a two-pipe system that draws combustion air (air
intake) from outdoors, and discharges exhaust gases to the
outdoors. Ensure that adequate separation is maintained
between the air intake inlet and the exhaust vent terminal. Refer
to the vent terminal configuration drawings in the "Vent
Termination" sections.
Flue gas exhaust to outdoors
Combustion air from outdoors. "Direct Vent"
installation: check air intake outside is clear of
obstructions.
Figure 13
Direct vent
22
Section: Installation
Summary of Contents for SL 10-85 G3
Page 8: ...Intentionally left empty ...
Page 14: ...Intentionally left empty ...
Page 66: ...Figure 49 Electric wiring connections 62 Section Installation ...
Page 78: ...Intentionally left empty ...
Page 92: ...Intentionally left empty ...
Page 106: ...Internal wiring diagram Figure 53 Internal wiring diagram 102 Section Appendices ...
Page 107: ...Sequence of Operation Figure 54 Sequence of Operation 103 Sequence of Operation ...
Page 109: ...105 Exploded views of boiler parts ...
Page 114: ...110 Section Appendices ...
Page 122: ...Intentionally left empty ...