4.4 I/O signals
4-14
4. Operation
[LS0] [LS1] signals: Position detection output
●
The LS signals perform the same operation as an air cylinder automatic switch.
They are not positioning complete signals.
●
The LS signals turn ON when the current ELECYLINDER position is within the
detection range configured at the backward and forward ends.
●
They turn ON when within the detection range regardless of whether the servo
is ON or OFF.
The backward end and forward end
set values' relationship to [LS0]
and [LS1] signals ON is as follows.
In this example, the LS signal
detection range is ±0.10mm.
To adjust the LS signal detection range,
open the [Edit parameters window].
Parameter No.2
[Auto switch LS signal detection range
adjustment] can be used to
make adjustments.
B
ackward end
0.00mm
Forward end
200.00mm
[LS0 detection range]
-0.10 to 0.10mm
[LS1 detection range]
199.90 to 200.10mm
(backward end/forward end)