Page 53
»
Attach plug (8) to the sensor electrode. (Knurled nut (9)
- gray)
»
Switch breaker back on.
»
Switch on the unit and check for leaks after 15-30 min-
utes of operation.
If leakage occurs, switch off power supply and follow safety
instructions for work on live components.
Note:
In the following cases:
•
the electrodes must be frequently replaced,
•
black slime collects inside the cylinder, or
•
there is "lightning" in the cylinder,
the conductivity of the water is too high or it isn't decanted often
enough. In this case please contact HygroMatik.
9.6 Cleaning the Blow- Down Pump
»
Remove cylinder
»
Detach e-cable from the pump.
»
Detach adapter (30) from the pump.
»
Loosen screws (44) and remove the pump from the
base.
»
Open the pump (bayonet lock).
»
Remove residues from the drain hoses and pump (if
neccessary replace o-ring (33) or
housing (34) if these
components are no longer in excellent condition).
»
Reassemble the pump.
»
Moisten o-ring (31) and insert in the side connection of
the base.
»
Push pump into the base and mount tightly with screws
(44).
»
Moisten o-ring (31) and insert in adapter (30).
»
Fit adapter (30) over the side connection of the pump.
»
Connect e-cable to the pump.
» Install
cylinder.
»
Switch on the unit and check for leaks during operation.
If leakage occurs, switch off power supply and follow safety
instructions for work on live components.