Page 15
5. Installation
Warning:
Installation of this unit to be attempted only by quali-
fied personnel. We accept no liability for damage due to faulty
installation.
Obey all safety notes and warnings present on the unit.
During installation the unit must be disconnected from its power
supply.
Attaching or installing additional components is permitted only
with the written consent of the manufacturer, or else the war-
ranty is void.
5.1 Steam Humidifier Operating Environment
Note:
When selecting the installation site for the steam humidi-
fier, note that:
•
Ambient temperature must be b5° and +40° C.
•
Relative humidity must not exceed 80% RH.
•
An Installation in a closed room requires aeration and if
neccessary temperature conditioning in order to reach
the above mentioned environmental conditions.
•
The minimum clearances indicated in the diagram
below must be observed; these are necessary to
ensure adequate ventilation for the housing.
•
HygroMatik humidifiers are not suitable for direct out-
door installation.
•
The steam humidifier should be installed as close as
possible to the steam manifold. Optimal performance is
guaranteed only with short lengths of steam and con-
densate hose
.
•
Hoses must be laid at a consistent 5-10% incline to pre-
vent sagging and kinking
.
•
The rear panel of the steam humidifier heats up during
operation (to a maximum of 60°C).
Take care that the
construction on which the unit is mounted is not made
of temperature-sensitive material.
•
Place the steam humidifier so that the unit is easily
accessible with sufficient space to perform mainte-
nance.
•
The steam humidifier is not qualified for exterior appli-
cations.