Page 51
Warning:
At the latest, electrodes must be replaced if a mainte-
nance message is displayed. The maintenance message
appears after one hour of operation at maximum water level.
The humidifier switches itself off. Also see Section "Mainte-
nance." When the electrodes are less than 1/3 to 1/2 of their
original length, replace them.
9.4.1 Original Electrode Lengths
Original lengths of HygroMatik large area stainless-steel elec-
trodes are:
HyLine:
CompactLine:
MiniSteam:
9.4.2 Uneven Electrode Lengths
In most case, the longer electrode(s) will not be supplied with
electricity for a time. Therefore they will not wear. The cause of
the problem, such as a tripped circuit breaker, can be repaired.
However, since the shorter electrode(s) have a greater specific
load, the electrodes continue to wear unevenly.
Note:
Replace electrodes with significantly uneven wear. Check
the power supply (breaker, voltage drop). Also see electronic
operation, Section "Malfunctions."
9.5 Replacing Electrodes
Type
HY05-HY08 HY13-HY60 HY90-HY116
Length [mm]
155
235
300
Type
C6 C10 C17-45 C58
Length [mm] 125 155
235
300
Type
MS5
MS10
Length [mm]
125
155