Other voltages are available on request.
We recommend employing medium blow main fuses (applicable
only to the grid voltages above). See table below indicating max-
imum power usage for each circuit protection:
When using fault current circuit breakers please use a separate
one for the humidifier.
HyLine:
CompactLine:
Type
Main Power Supply
HY05 - HY45
1 x 400V/3Phase/N
HY60 - HY116
2 x 400V/3Phase/N
CompactLine
1 x 400V/3Phase/N
MS5, MS10
1 x 400V/3Phase/N
MS5
1 x 230/1Phase/N
DBE 2
1 x 230V/1Phase
DBE 6-45
1 x 400V/3Phase/N
Type
Power Usage
Circuit Protection
HY05
5,4 A
3 x 6A
HY08
8,7 A
3 x 10A
HY13
14,1 A
3 x 16 A
HY17
18,4 A
3 x 20 A
HY23
24,9 A
3 x 35 A
HY30
32,5 A
3 x 35 A
HY45
48,8 A
3 x 63 A
HY60
2 x 32,5 A
6 x 35 A
HY90
2 x 48,8 A
6 x 63 A
HY116
2 x 62,8 A
6 x 63 A
Type
Power Usage
Circuit Protection
C6
6,5 A
3 x 10 A
C10
10,8 A
3 x 16 A
C17
18,4 A
3 x 20 A
C22
23,8
3 x 35 A
C30
32,5 A
3 x 35 A
C45
48,8 A
3 x 63 A
C58
62,8 A
3 x 63 A