5.2 Fan Unit (optional)
Note:
The fan unit should be positioned to avoid drafts. In gen-
eral, a minimum height of 2 m is sufficient.
•
Install the fan unit directly on a wall.
5.2.1 Fan Unit Type VG
•
Install the fan unit over the steam humidifier.
•
When employing multiple fan units, do not exceed a
maximum distance of 5 m from the steam humidifier.
•
Observe the clearances specified in the diagram below:
Fan Unit
Type
for wall installation VG 08, 17, 30
Technical Specifications Fan Unit VG
Fan Unit
VG08
VG17
VG30
Quantity of Steam
[kg/h]
8
17
30
Steam Inlet
[mm
φ
]
25
25
40
Condensate Outlet
[mm
φ
]
12
12
12
Airflow Capacity
[cbm/h]
185
185
350
Nominal Output
[W]
35
35
67
Nominal voltage
[V]
230
230
230
Dimensions
W [mm]
441
507
550
H [mm]
171
171
171
D [mm]
180
237
277
Weight
[kg]
4,5
6
7
Steam
Front View Wall Installation
Side View Wall Installation