Page 31
»
If enough space is available, lay a loop as a vapor trap.
The steam manifold must be at least 500 mm from the
loop.
If the steam manifold is positioned lower than 500 mm
above the steam humidifier:
»
Lay steam hose at a height of at least 400 mm above
unit and then connect to the steam manifold with a con-
stant fall.
»
Lay condensate hose with a loop of 200 mm diameter
(vapour trap) to the drain. The distance between vapour
trap and steam manifold should have at least 500mm.
»
Lay the loop of condensate hose 200 mm directly
above the drain. Detail x