background image

 

 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 

 
 

 

VapaLite 

Humidifier 

Models LMV2 & LMV4 

 
 
 

Please read these Instructions 

BEFORE 

Installation and Start-up 

Failure to observe manufacturer’s recommendations may invalidate warranty 

 
 
 
 
 

 

Installation in countries covered by EC Directives: 

This product meets the requirements of the RoHS Directive 2002/95/EEC 

This product will meet the requirements of the Low Voltage Safety Directive 2006/95/EEC and the EMC Directive  

2004/108/EEC when installed in accordance with the instructions contained in this manual. 

Failure to comply with these instructions may invalidate the manufacturer's warranty or any certificate/declaration 

of conformance requested to be supplied with the unit. 

 
 
 
 

Vapac Humidity Control Limited reserves the right to change the design or specification  

of the equipment described in this manual without prior notice. 

 
 
 
 
 

Vapac equipment is manufactured in England by: 

Vapac Humidity Control Limited 

 

®

 

Summary of Contents for VapaLite LMV2

Page 1: ...w Voltage Safety Directive 2006 95 EEC and the EMC Directive 2004 108 EEC when installed in accordance with the instructions contained in this manual Failure to comply with these instructions may invalidate the manufacturer s warranty or any certificate declaration of conformance requested to be supplied with the unit Vapac Humidity Control Limited reserves the right to change the design or specif...

Page 2: ...ers etc DON T mount unit in an unventilated enclosure DON T mount in a position requiring ladder access to the unit DON T install the unit behind a false ceiling or other situation where an unusual malfunction eg water leak would cause damage DON T install the unit in an area which will be hosed down DON T install the unit where the ambient air temperature can exceed 35 C DON T mount the unit insi...

Page 3: ... for 100 C DO arrange to discharge drain water from the unit into a vented and trapped drain at a position where flash steam rising from the drain line tundish will not pose a problem for the Vapac or other equipment DO provide adequate fall for the drain pipework to allow free flow of water drained from each unit DO ensure drain line pipe size will accommodate water being drained at the same time...

Page 4: ...20 for condensate to drain back to the steam cylinder or down to a condensate separator Always provide a continuous slope DO provide adequate support to prevent sagging Fit pipe clips every 30 50cm Support straight lengths on cable trays or in heat resistant plastic pipe DO use a Vapac condensate separator or simple trapped pipe connection to drain off condensate from extended steam lines DO ensur...

Page 5: ... Connection Releasing the Electrical Section To make the electrical connections to the unit it is necessary to detach the electrical section To do this open the door disconnect the hose and the electrode caps from the steam cylinder then remove the steam cylinder from the cabinet by lifting it out of the manifold Next undo and remove the two screws which hold the electrical panel to the outer cabi...

Page 6: ...ntified as High Over current STOP Drain Fault STOP no drain function Feed Fault STOP water not reaching cylinder The stop condition on the VapaLite PCB will be cleared by switching the unit off and on When a stop condition occurs follow the service and maintenance procedure to inspect the steam cylinder and the drain pump User LEDs Description 1 OFF Unit in shutdown 2 OFF Unit in standby 3 Green A...

Page 7: ...vent material lodging in the valve seat or blocking the small flow control restrictor which is fitted in the valve Fault Service Indications Requiring Operator Intervention User LED 1 State Description 1 AMBER Drain fault 2 AMBER flashing 1 second period Feed fault 3 AMBER flashing 2 second period Over current fault 4 GREEN Service now 1 2 3 Fault Stop Once the problem has been cleared the fault c...

Page 8: ...l cup internal u tube Drain Fault Check drain pump operates check when draining the water runs to drain and doesn t return to the cylinder via the Tundish fill cup blocked internal drain hose or problem with the Tundish fill cup internal u tube Over Current Fault check the unit drains correctly check the cylinder electrodes are not damaged or mis aligned in the cylinder VapaLite Specification Mode...

Page 9: ...9 ...

Page 10: ...10 Vapac Humidity Control Ltd Fircroft Way Edenbridge Kent TN8 6EZ Tel 01732 863447 Fax 01732 865658 www eaton williams com INSTALLATION NOTES ...

Reviews: