SPA
Page 75
X X
Maintenance K1
System operation
continues. Green
LED rapidly flash-
ing.
•
According to manufacturer specification 90%
of the electrical lifetime is achieved. To avoid
failure, a replacement of the main contactor is
recommended in the short term.
•
•
Replace main contactor.
See parameter description "P11 re-
set main contactor interval" for
Comfort / Comfort Plus control or
"Brief Description of Jumpers" for
Basic control.
X X
Safety stop
•
Paramater D5 for limitation of operating time
is activated. Steam generator stopped opera-
tion after the safety interlock was closed for
the time set in parameter D5.
•
•
By opening and closing the safety
interlock the steam generator re-
starts operation for the number of
hours programmed in D5.
Alternatively, set D = 0 and restart
system. Function „Operating time
limitation“ is now deactivated.
LED Dis-
play
H
L
***
H
y,C***
Message / Mal-
function Dis-
played*
Probable Cause
Resolution
HL
*
**
Hy
,C
**
*
Possible Condi-
tions
Probable Cause
Resolution
X X
Water is collecting
on the base plate
•
Cylinder improperly assembled after mainte-
nance:
-O-Ring has been damaged, has not been re-
placed, or has not been inserted
- Flange ( slot / spring) is damaged
- Flange has not been sealed properly
-
Mineral deposits in the flange.
•
Clean cylinder and install properly.
•
The cylinder is incorrectly placed on the base.
•
Lay a moistened new o-ring in the
base and then insert the cylinder.
•
The water cannot drain away during flushing.
•
Make sure drain is unobstructed.
X X
Water is leaking
from upper part of
steam cylinder.
•
Hose clamps on the steam or condensate
hose do not close tightly.
•
Tighten hose clamps.
•
The heater element or thermo sensor has not
been properly installed.
•
Install heater element and thermo
sensor as specified in the manual.
•
Steam hose adapter has not been correctly
installed or o-ring has not been changed.
•
Replace o-ring and correctly install
steam hose adapter.
•
If condensate is not into the steam cylinder,
the condensate connection must have a con-
densate plug.
•
Install condensate plug.