** Only Comfort- DS / Comfort Plus- DS
*** Hy, C = Electrode Steam Generator, HL = Heater Element Steam
Generator
X
Light / sparks in
the cylinder
•
•
The appearance of light or sparks sug-
gests rapid loss of electrode material
(brown-black deposits) and very high wa-
ter conductivity.
In these cases, consult HygroMatik.
Blow-down pump is not working properly
or is defective.
•
·
•
Deactivate the unit immediately
to prevent it from being dama-
ged.
Perform maintenance:
- Replace electrodes
- Clean steam cylinder
- Check water quality or conduc-
tivity, also see Section „Direc-
tions for Use“.
Increase blow-down frequency
and/or blow-down volume.
Check blow-down pump func-
tion and replace blow-down
pump if necessary. See mes-
sage
Blow-Down Fault
HL
**
*
Hy
,C
**
*
Possible Condi-
tions
Probable Cause
Resolution
* :