8. Fault Messages (Comfort- DS / Comfort
Plus- DS und Basic- DS)
The control Comfort- DS / Comfort Plus- DS and also Basic-DS con-
stantly monitor all important functions of the humidifier. In the case of a
fault the humidifier switches off.
In case of a malfunction, the red LED blinks on the display and operat-
ing panel and one of the following messages is displayed (depending
on unit type):
(also see chapter „Faults and Messages“)
Fault °C sensor
If the recorded temperature remains outside the allowable temperature
range of 0°C/32°F to 130°C/266°F (50.4 to 0.42 kOhm) for longer than
5 minutes, the control displays
Fault °C sensor
.
Fault °C Max
If the recorded temperature is higher than the maximum allowed cabin
temperature for longer than 60 seconds, the control displays
Fault °C
Max
and deactivates the steam generator.
Blow-Down Fault
The control periodically activates the blow-down pump. If no water or
insufficient water is flushed out during blow-down, the control displays
Blow-Down Fault
.
Unit Type
Fault Name
HyLine,
CompactLine,
MiniSteam
HeaterLine, Heater-
Compact
Blow-down fault
F1
x
x
Thermo sensor activated
F2
x
Max.-level
F3
x
Fault filling
F4
x
x
RH Sensor fault
F6
x
x
Fault Sensor
F7
x
Maintenance
F8
x
System Failure
F9
x
x
Fault main cont.
F10
x
x
Steam-down time
F11
x
Fault °C max.
F12
x
x
Lost Ground Control
x
x