5.3.2.1 Control Parameters Submenu (under Startup
Menu)
Summary of Parameters:
Programming sequence to modify the control parameters.
The steps below make an essential change to a control parame-
ter. If this is not intended, be sure to reestablish the original set-
ting after changing it for exercising purposes. In any case, be
aware of what yor are doing!
Task: Parameter U6 is to be changed from “internal PI-controller”
to “1-step”.
»
press
in Operating Mode,
»
press
or
until “Commissioning Parameters”
appears on the display
»
press
»
press
»
press
»
press
»
press
Para-
meter
Description
Possible Settings
Access
Code
U6
Controls
1 Step (On/Off)
MODBUS
Mehrstufig
internal PI-controller
010
P1
Steam generation
output limiter [%]
25-100%
010
E1*
Xp-PI-controller
=100/E1
[Amplification]
[0- 100 %]
010
E2*
Tn-PI-controller
[Integration time]
[0- 255sec.]
010
* Only when internal PI-controller is activated
Please note
Sprache/Language
ESC
Commissioning
Parameters
ESC
Commissioning
Parameters
Code 000
ESC
Commissioning
Parameters
Code 000
ESC
Commissioning
Parameters
Code 010
ESC
Commissioning
Parameters
Code 010
ESC