11. Commissioning
Risk of electrical shock!
Hazardous high electrical voltage!
Start-up of the unit is restricted to expert staff only (electricians or
expert personnel with equivalent training).
Step 1: Check of mechanical integrity
»
Check cylinder seating.
»
Check steam and condensate hose clamps.
Step 2: Check of electrical wire connections
»
Check that all electrical wire connections (including steam
cylinder wiring) are tight and secure.
Step 3: Switching on the steam humidifier
»
Switch on main breaker.
»
Open water supply stopcock (operating pressure should be
1bar min., 10bar max./14.5 psi min., 145 psi max.).
»
Switch on unit by setting control switch to “I”.
Step 4:
The unit performs a self-tes
t
•
The LEDs on the control panel light up briefly in succession
.
•
Subsequently, the blow-down pump is activated for a few
seconds. This step checks pump operation and partial water
exchange during restart (applies only to electrode steam
humidifiers)
•
After self-tests are completed, the display reads:
For the next steps, the
safety interlock
must be closed (see also
chapter „Remote Switch / Safety Interlock) and the
temperature set-
point
must be higher than the actual cabin temperature.
Step 5: Normal operation starts
the water solenoid valve opens and feeds water into the
steam cylinder
Initiation of steam production may take up to 20 mins
»
Let all electrically-driven operations run to completion.
HygroMatik (R)
Self Test
LED Test
HygroMatik (R)
Self Test
Partial blow-down
Steam Bath
X.X °C
°C F E l
Please note