6.2.2 Steam Bath Parameters (G0 - G9, G13)
Steam bath Parameters G0 - G9 and G13 can only be accessed on the
parameter lists with a code (Code 010).
6.2.2.1 Calibration °C Actual °C (G0)
Using this Parameter, one can calibrate the temperature sensor con-
nected to terminals 6 and 7.
The sensor is calibrated at the factory. Readjustment with a 2nd. tem-
perature gauge is possible within a range of -5K to +5K.
6.2.2.2 Hysteresis Controller (G1)
Using this parameter, you can modify the differential between the acti-
vation and deactivation points of the temperature controller. The steam
generator shuts off at a temperature of
Steam Bath °C Set Value (G2)
+ Hysteresis Controller (G1)
.
Example:
G2 is set to 45°C and G1 is set to 1 K. The steam generator
shuts off at 46°C/114.8°F and switches on again at 45°C/113°F.
The preset value for G1 is 1K.
6.2.2.3 Steam Bath °C Set Value (G2)
Using this parameter, you can set the desired temperature in the steam
bath. Changes to this setting in Operating Mode are saved when the
steam generator is switched off.
Please note
Please note
45°C/ 46°C/
113°F 114.8°F