7.
Mechanical assembly
Caution:
The device may only be assembled by qualified staff.
HygroMatik accept no liability for damages resulting from incor-
rect assembly.
Observe all safety instructions and warnings found on the
device. The device must be de-energised during assembly.
Mounting or insertion of additional devices is only permitted with
the written consent of the manufacturer. Otherwise the guaran-
tee and warranty will become void.
7.1
Overview of the humidification chamber
1: Vortex module wall with spray system
2: Droplet separators
3: Upper guide rails for droplet separators
4: Lower guide rails for droplet separators
5: Collection tray
6: Drain with trap
7. Guide rails for vortex module wall
8. Humidification section, >/= 0.9 m
9. Two supplied bushings for the duct (for partial-load / full-load
switching) for connecting high-pressure hoses * Only one bush-
ing is needed for the standard model.
10. Distribution pipe
Note:
In front of the vortex module wall and from the droplet
separators a minimum distance of 0.3 m to other installed com-
ponents must be maintained (see above schematic). In case of
an upstream installation of a fan in front of the vortex module
wall, the minimum distance shall be 1 m or appropriate action
has to be taken in order to ensure a laminar flow of the vortex
module wall. Temperatures higher than 60°C may destroy the
vortex modules.
Summary of Contents for LPS
Page 1: ...LPS Humidifies and Cools ÁLPS Ä4 3Ö ENhÈ LPS 20130619 EN Operating manual ...
Page 37: ...Page 37 8 Dimensions Pump Station View from below Side view Rear view ...
Page 62: ...Page 62 14 2 3 1 Menu structure and parameter setting 4 3 ...
Page 63: ...Page 63 15 EC declaration of conformity ...
Page 69: ...Page 69 4 3 ...