Page 51
1. Set the main switch on the control panel of the HygroMatik
nozzle system LPS to '0'.
2. Close the (external) stopcock.
3. Relieve the line pressure.
4. Open the filter housing by hand. The threads may be dam-
aged if pliers are used.
5. Clean the filter housing.
6. Replace the filter cartridge (if necessary).
7. Screw the filter housing into the seat by hand.
Note:
Do not pinch the sealing ring.
8. Open the external stopcock.
9. Set the main switch to 'I'.
13.1.2
Cleaning the atomizer nozzle
1. Switch the HygroMatik LPS Nozzle System power supply to 0
2. Unscrew the nozzle from nozzle holder. Take care not to touch
the impact pin.
3. Unscrew the nozzle by screwing the inside part out.
4. Clean the nozzle components in an ultrasonic bath for about
10 minutes, if necessary use a lime remover in low concentra-
tion (less than 10%).
5. Put nozzle components back together.
6. Screw nozzle in the nozzle holder.
7. Switch power switch back to I
8. Finally check spray pattern
Caution
: Make sure that the pressure reduces by, for instance,
activating the wash cycle.
Caution:
Wear eye protection when cleaning the nozzle.
Caution:
Use only an appropriate tool to remove the nozzles.