Page 16
4.3
Partial and Full-Load
For optimal humidification control under various input conditions
the HygroMatik nozzle system LPS can be equipped with a „Par-
tial and Full-Load” control function.
At Full-load all nozzles are fed with water. At Partial-load a sole-
noid valve switches off the water supply for approximately half
of the nozzles.
Construction
:
The vane pump has to exits for water - one is the water supply
for the nozzles for Partial load and the othe one is the water sup-
ply for the nozzles for Full load.
If the external control signal decreases below a special switching
point, the HygroMatik nozzle system LPS switches off the water
supply for half of the nozzles.