Page 23
7.3.2
Examplary design of guide rails for a vortex
module wall
Pos. 1: upper guide rail
Pos. 2: vortex module wall
Pos. 3: spacer or direct connection floor of chamber
Pos. 4: lower guide rail
Pos. 5: humidification chamber
Inner dimension of guide rail: 62 mm
Hight: please see above sketch
Material: 1.4301 stainless steel sheet, thickness: 1 mm
7.3.3
Side rails for the vortex module wall:
If the wall consists of 11 or more vortex module rows side rails
are required in order to avoid bending of the vortex module wall.
Having more than 16 vortex modules in horizontal position the
the vortex module wall has to be vertically separated into two
halfs, that are separately fixed by side rails
Guide rail (cross section)
Summary of Contents for LPS
Page 1: ...LPS Humidifies and Cools ÁLPS Ä4 3Ö ENhÈ LPS 20130619 EN Operating manual ...
Page 37: ...Page 37 8 Dimensions Pump Station View from below Side view Rear view ...
Page 62: ...Page 62 14 2 3 1 Menu structure and parameter setting 4 3 ...
Page 63: ...Page 63 15 EC declaration of conformity ...
Page 69: ...Page 69 4 3 ...