The following reading parameters can be selected in the reading
level:
L01
Actual value of pressure [bars]
L03
Actual value of the control signal
L04
Setpoint control signal
L05
Set value of performance limiter [%]
L06
Set value for the target humidity (only valid
with PI control [%]
L07
Actual value of current humidity (only valid
with PI control [%]
L11
Total running time of pump [h]
L13
Total running hours [h]
L14
Remaining running time before next service
reminder [h]
L15
Remaining time until standby-draining [hh:mm]
14.2.2.2
Programming level:
The following parameters can be changed in the programming
level:
Parameter Designation
Option
Factory setting
U6
Controls
0 = external controller
0
1 = single-stage/ On-Off
2= PI control
L06
Setpoint rel. humidity
10-100%
50%
(only activ if U6=2)
L05
Output limitation
25-100%
100%
r_S
Reset „Service” message ON/OFF
OFF
C12
Integral part,
50-500
100
with PI humidity controller
C11
Proportional part,
50-200
100
with PI humidity controller
E03
External control signal
4 = 0-10V DC
4
3 = 4-20mA DC
Summary of Contents for LPS
Page 1: ...LPS Humidifies and Cools ÁLPS Ä4 3Ö ENhÈ LPS 20130619 EN Operating manual ...
Page 37: ...Page 37 8 Dimensions Pump Station View from below Side view Rear view ...
Page 62: ...Page 62 14 2 3 1 Menu structure and parameter setting 4 3 ...
Page 63: ...Page 63 15 EC declaration of conformity ...
Page 69: ...Page 69 4 3 ...