ContaminationSensor CS 1000
Analog output
HYDAC FILTER SYSTEMS GMBH
en(us)
Page 66 / 108
BeWa CS1000 3247149p 240 en-us 2011-02-11.doc
2011-02-11
ISO + T
The ISO+T signal consists of 4 measured values which are transmitted time-coded
with the following time slices:
4,0
2,0
4,1
2,05
I (mA)
U (V)
time (ms)
4,8
2,4
19,2
High
High
Low
Low
9,6
300
3000
3000
3000
1
2
4
6
8
3
5
7
19,5
9,85
4,3
2,15
19,7
9,75
0,0
19,8
9,9
_
Ti
me
Signal
Size
Signal duration
per pulse
in ms
Current (I) / Voltage (U)
1
Identifier
>4µm
(c)
300
High / Low
2 Measured
value
>4µm
(c)
3000
Current/Voltage for measured value
3
Identifier
>6µm
(c)
300
High / Low / High / Low
4 Measured
value
>6µm
(c)
3000
Current/Voltage for measured value
5
Identifier
>14µm
(c)
300
High / Low / High / Low / High / Low
6 Measured
value
>14µm
(c)
3000
Current/Voltage for measured value
7
Identifier
Temperature
300
High / Low / High / Low / High / Low / High /
Low / High / Low
8 Measured
value Temperature
3000
Current/Voltage for measured value