ContaminationSensor CS 1000
CS1000 hydraulic installation
HYDAC FILTER SYSTEMS GMBH
en(us)
Page 24 / 108
BeWa CS1000 3247149p 240 en-us 2011-02-11.doc
2011-02-11
Hydraulic connection of the CS1000
NOTICE
Working overpressure
The CS will be destroyed.
►
Observe the maximum operating pressure on the CS 1000 type label.
Observe the following sequence when connecting the sensor to the hydraulic
system:
1.
First, connect the return line to the OUTLET port of the CS. Connection
thread: G1/4 ISO 228, recommended diameter of line:
≥
4 mm.
2.
Now connect the other end of the return line to the system tank, for
example.
3.
Check the pressure at the measurement point. It has to be within the
permissible range.
4.
Now connect the measurement line to the INLET of the CS.
Connection thread: G1/4 ISO 228, recommended diameter of line
≤
4 mm
(to prevent particle sedimentation).
If there are particles larger than 400 microns in the hydraulic system, or
this is to be expected, a strainer has to be installed upstream of the CS1000
(e.g. CM-S).
5.
Now connect the other end of the measurement line to the measurement
point.
Oil starts to flow through the sensor as soon as it is connected to
the pressure line. That is why it is necessary to connect in the sequence
specified above.
6.
The hydraulic installation of the CS is now complete.