Commissioning
Chapter 2
OPERATION MANUAL
V1.2.0en/12.05.15//14.06
Liability for errors and misprints excluded.
Unistat® T300 Series
25
2.9.2.2
Removing the Isolating sleeve (only for externally closed applications)
PROCEDURE
Remove the
>Expansion vessel cap<
[22].
Remove the
>Isolating sleeve<
[27]. The permanently fitted
>Guide rod<
[A] remains in the
housing.
Close the
>Expansion vessel cap<
[22].
Fasten the
>Isolating sleeve<
[27] at the place provided on the housing-side of the temperature
control unit.
Open all valves, in case of standard devices the
>Venting valve expansion vessel<
[21] by turning
them anti-
clockwise (turn 90° left as far as it will go).
2.10
Connecting externally closed/open application
The illustration “Wiring diagram” can be found on page 89 in section
.
2.10.1
Connecting an externally closed application
Operating an externally closed system with >Isolating sleeve< [27] installed
BURSTING DUE TO OVERPRESSURE DURING TEMPERATURE CONTROL.
Shut down the temperature control unit immediately.
Allow the thermal fluid to cool to room temperature.
Prior to starting up the temperature control unit with an externally closed system, remove the
>Isolating sleeve<
[27] (see page 24, in section
»Mounting/removing the isolating sleeve (op-
).
Open all valves, in case of standard devices the
>Venting valve expansion vessel<
[21] by turn-
ing them anti-
clockwise (turn 90° left as far as it will go).
Pressure > 0.5 bar (g) with glass apparatus
MATERIAL DAMAGE CAUSED BY CRACK FORMATION AT THE GLASS APPARATUS.
Provide an over-pressure protective device to prevent damage to the glass apparatus.
Do not install valves/quick-release couplings in the feed/discharge lines from the temperature
control unit to the glass apparatus and from the glass apparatus to the temperature control
unit.
If valves/quick-release couplings are required:
Install burst disks on the glass apparatus itself (at the feed and discharge lines).
Install a bypass upstream of the valves/quick-release couplings for the glass apparatus.
Matching accessories (e.g. bypasses to reduce pressure) can be found in the Huber catalog.
Remove the Isolating
sleeve
Example: Connecting
an externally closed
application