Before you transfer the UPS from maintenance bypass mode to normal mode, ensure that the
bypass input and output are normal.
Procedure
Step 1
Turn off the maintenance bypass switch.
Rotate the maintenance bypass switch to the OFF position, as shown in
. The
Maint. breaker closed
alarm disappears from the alarm list. View the system running
diagram on the LCD or WebUI to check that the UPS has transferred to bypass mode.
Figure 5-18
Turning off the maintenance bypass switch
Step 2
Start the inverter.
----End