UPS5000-E-(25 kVA-75 kVA)-SM
User Manual (Half Height)
3 Installation
Issue 03 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
62
Figure 3-25
Preparing a cable terminal outside the cabinet
Choose an appropriate cabling route based on the actual situation. The figure is for reference only.
Step 4
Connect the cable with a crimped terminal to the corresponding copper bar.
Step 5
Clean foreign matter inside the cabinet.
----End
3.2.6 Routing Cables
3.2.6.1 Cable Routes
Procedure
Step 1
Remove the PDU cover.
Figure 3-26
Removing the PDU cover
Step 2
Route power cables.