UPS5000-E-(25 kVA-75 kVA)-SM
User Manual (Half Height)
4 LCD and WebUI
Issue 03 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
96
Batt. sharing
affects the actual discharge current and the estimated discharge time.
Incorrect settings will cause a high or low charge current, which tends to damage batteries.
An incorrect estimated discharge time may cause a data backup failure.
When
Single/Parallel
is set to
Single
, the
Batt. sharing
parameter is unavailable.
Retain default values for the
Cur. Limit coef.
and
Cell float volt.
parameters. Only
professional maintenance personnel can change the values.
Figure 4-19
Battery Settings Screen
Basic Parameters
Figure 4-20
Basic Parameters screen
Item
Description
Default Value Value Range
Single batt.
volt.
Specifies the voltage of each
battery that is connected in the
battery string in series.
12 V
2, 6, 12
Single batt.
cap.
Specifies the capacity of each
battery that is connected in the
battery string in series.
Depends on the
actual model.
5–9999
Batteries in
Specifies the number of batteries
The default
value depends
The value range
depends on the