UPS5000-E-(25 kVA-75 kVA)-SM
User Manual (Half Height)
4 LCD and WebUI
Issue 03 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
80
Indicators
Table 4-1
Indicator description
Indicator
Color
Status
Meaning
Mains indicator
Green
On
The UPS is in normal mode.
Off
The UPS is not in normal mode.
Battery indicator
Yellow
On
The UPS is in battery mode.
Off
The UPS is not in battery mode.
Blinking
The remaining battery capacity is less
than the threshold.
Bypass indicator
Yellow
On
The UPS is in bypass mode.
Off
The UPS is not in bypass mode.
Fault indicator/INFO
button
Red
On
The UPS is faulty.
Red
Blinking
The UPS generates an alarm.
Green
On
The UPS is running properly.
The UPS is in mains ECO mode when the mains indicator and bypass indicator are both on.
The UPS is in battery ECO mode when the battery indicator and bypass indicator are both on.
Functions
The LCD displays the UPS running data and alarm information, and allows you to set
parameters and control UPS running. The backlight turns off if you do not press any button
within 30s.
Table 4-2
Button description
Button Meaning
Description
ESC
Back/Shutdown
On any screen other than the default screen, press
ESC to return to the upper-level menu (the default
screen is the upper-level screen for the main menu
screen).
On the default screen, press ESC for more than 5s.
Release the button when you hear a beep sound.
On the shutdown screen displayed, press
.
The inverter shuts down.
▲
Up
Press ▲ or ▼ to scroll upward or downward.
Set parameters by using the list or step increase or
decrease.
▼
Down