UPS5000-E-(25 kVA-75 kVA)-SM
User Manual (Half Height)
3 Installation
Issue 03 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
42
Item
25 kVA
50 kVA
75 kVA
connector
Recommended
cross-sectional
area (mm
2
)
L1
4 x 10
4 x 25
4 x 50
L2
L3
N
PE
10
25
25
Output
connector
Output current (A)
38
76
114
Recommended
cross-sectional
area (mm
2
)
U
4 x 6
4 x 16
4 x 25
V
W
N
PE
6
16
25
Battery
input
connector
Nominal discharge
current (A)
69
138
206
Maximum discharge
current (A)
83
165
247
Recommended
cross-sectional
area (mm
2
)
+
35
50
95
N
-
PE
16
25
50
When installation environment (such as routing mode and ambient temperature) changes,
prepare cables based on specifications in IEC60364-5-52 or local standards.
When the mains input and bypass input share a power source, configure mains input
power cables as input power cables. The cables listed in
the following requirements are met:
−
The cables are installed along the wall or on the floor (IEC60364-5-52 C standards).
−
The ambient temperature is 30°C.
−
The AC voltage loss is less than 3%, and the DC voltage loss is less than 1%. The
recommended cross-sectional areas in
meet the basic through-current
requirements. Users should evaluate the line voltage loss based on the actual cable
length. If the voltage loss exceeds the requirements, increase the cable
cross-sectional areas properly.
−
90°C copper-core cables are used.
When selecting, connecting, and routing power cables, follow local safety regulations
and rules.