UPS5000-E-(25 kVA-75 kVA)-SM
User Manual (Half Height)
4 LCD and WebUI
Issue 03 (2019-12-13)
Copyright © Huawei Technologies Co., Ltd.
99
Figure 4-24
Shallow Discharge Test screen
Item
Description
Default Value Value Range
Scheduled test
When certain conditions are met,
the charger shuts down, the UPS
transfers from normal mode to
battery mode, and batteries
supply power to loads. The UPS
records the battery discharge data
as a reference for battery reserve
and lifespan.
Disable
Disable, Enable
Time
The shallow discharge test starts
in the specified time.
00:00–06:00
00:00–06:00,
06:00–12:00,
12:00–18:00, or
18:00–24:00.
Time interval
Indicates the time interval for
shallow discharge tests The
parameter is configurable in any
mode.
60d
30d–90d
Discharge ratio
Indicates the proportion of the
discharge capacity to the total
discharge capacity. The
parameter is configurable in any
mode.
20%
10%–50%
Backup time
Figure 4-25
Backup time screen
−
Warning thresh.
parameter