Figure 5-31 Bundling communications cables
Step 5 Tighten the thread-lock sealing nut and seal the cable gland.
----End
5.6.3 (Optional) Installing the Solar Tracker Power Cable
Precautions
NO TICE
● A switch-disconnector-fuse or fuse-switch-disconnector with a voltage of no
less than 500 V, current of 16 A, and protection type of gM needs to be
installed between the SUN2000 and the tracker controller for protection.
● The cable between the wiring terminal on the power cable and the switch-
disconnector-fuse or fuse-switch-disconnector should be less than or equal to
2.5 meters.
Cable Specifications
Recommended: dual-layer three-core outdoor copper cable with a conductor
cross-sectional area of 10 mm
2
.
WARNING
Do not place flammable materials around the cable.
Procedure
Step 1 Remove an appropriate length of the jacket and insulation layer from the tracking
power cable using a wire stripper. (Ensure that the jacket is in the maintenance
compartment.)
SUN2000-(60KTL, 65KTL)-M0
User Manual (Mexico Edition)
5 Electrical Connections
Issue 06 (2020-10-12)
Copyright © Huawei Technologies Co., Ltd.
58