SOLAR300 - SOLAR300N
EN - 63
5.4.2.11. Flicker
This option permits to set control parameters relative to flicker value recordings on the
input voltages in compliance to EN 61000-4-15 and EN 50160 standards (see § 10.7). In
particular the below parameters are shown by meter:
Pst1’ = short term severity at 1 min; Pst = short term severity for all recording duration.
Plt = long term severity for all recording duration.
The below screen is shown:
Fig. 93: Flicker setting screen
For flicker recording at least one voltage selection and a correct integration period are
necessary conditions. In particular if no voltage are selected the below screen is shown:
Fig. 94: Flicker setting screen - no selected voltage
See the § 5.4.2.6 to exit from this error situation. In case of integration period setting value
less of 1 minute or higher to 15 minutes
the below error screen is shown by meter:
Fig. 95: Flicker setting screen - wrong period for flicker
See the § 5.4.2.4 to exit from this error situation. Press
SAVE
or
ENTER
keys (or the
smart icon
) to save each selection and confirm by “Ok” . The main screen is shown by
meter at the end of the operation. Press
ESC
key (or the smart icon ) to quit without
saving and go back to previous screens.
Summary of Contents for SOLAR300
Page 1: ...Copyright HT ITALIA 2017 Release EN 2 10 02 05 2017 SOLAR300 SOLAR300N User manual...
Page 2: ......
Page 159: ......