10.5.2. Limit values for harmonic voltage
EN50160 standard fixes the limits for the harmonic voltages, which can be introduced into
the network by the power supplier. In normal conditions, during any period in a week, 95%
of the RMS values of each harmonic voltage, mediated on 10 minutes, shall be lower than
or equal to the values stated in the following table. The total harmonic distortion (THD) of
the supply voltage (including all the harmonics up to 40
th
order) must be lower than or
equal to 8%.
ODD HARMONICS
EVEN HARMONICS
Not multiple of 3
Multiple of 3
Order h
Relative voltage %Max
Order h
Relative voltage % Max
Order h
Relative voltage % Max
5 6 3 5 2 2
7 5 9 1,5 4 1
11 3,5 15 0,5 6..24 0,5
13 3 21 0,5
17
2
19
1,5
23
1,5
25
1,5
Table 17: Reference values for harmonics voltage in compliance to EN50160
These limits, theoretically applicable only for the suppliers of electric energy, provide
anyway a series of reference values within which the harmonics introduced into the
network by the users must be contained
10.5.3. Presence of harmonics: causes
Any apparatus that alters the sine wave or uses only a part of such a wave causes
distortions to the sine wave and therefore harmonics.
All current signals result in some way virtually distorted. The most common situation is the
harmonic distortion caused by no-linear loads such as electric household appliances,
personal computers or speed control units for motors. Harmonic distortion causes
significant currents at frequencies that are odd multiples of the fundamental frequency.
Harmonic currents affect considerably the neutral wire of electric installations.
In most countries, the mains power is three-phase 50/60Hz with a delta primary and star
secondary transformers. The secondary generally provides 230V AC from phase to neutral
and 400V AC from phase to phase. Balancing the loads on each phase has always
represented an headache for electric system designers.
Tracing back to ten years ago, in a well balanced system, the vectorial sum of the currents
in the neutral was zero or quite low (in view of the difficulty to get a perfect balance). The
devices were incandescent lights, small motors and other devices that presented linear
loads. The result was an essentially sinusoidal current in each phase and a low current on
the neutral at a frequency of 50/60Hz.
“Modern” devices such as TV sets, fluorescent lights, video machines and microwave
ovens normally draw current for only a fraction of each cycle thus causing non-linear loads
and subsequent non-linear currents. All this generates odd harmonics of the 50/60Hz line
frequency. For this reason, the current in the transformers of the distribution boxes
contains only a 50Hz (or 60Hz) component but also a 150Hz (or 180Hz) component, a
50Hz (or 300Hz) component and other significant components of harmonic up to 750Hz
(or 900Hz) and higher.
The vectorial sum of the currents in a well balanced system that feeds no-linear loads may
still be quite low. However, the sum does not eliminate all current harmonics. The odd
multiples of the third harmonic (called “TRIPLENS”) are added together in the neutral and
can cause overheating even with balanced loads.