25
WFS 101545 Operations Manual
This page permits the operator to select the trip point for when an alarm notification
will be triggered. It can be used to notify when the filter needs to be switched over. It
can provide notification if a critical process parameter is exceeded. For instance, if a
maximum temperature for the process water was 75
o
F the TEMP ALARM could be set
for that temperature and would trigger an alarm if it was exceeded.
Factory Set Points:
RECIRC TEMP 80
o
F
RECIRC PRESSURE 63 PSI
PROCESS LOW FLOW 7 GPM
PROCESS PRESSURE 63 PSI
SPINDLE LOW FLOW 7 GPM
SPINDLE TEMP 80
o
F
vi.
Alarms
Audible alarms are triggered when a parameter is outside of the ALARM SET-POINT
operating window or if a leak is detected. The ALARM PAGE displays which specific
parameter is initiating the alarm and allows the alarm to be disabled. Figure 5-9
FIGURE 5-9