2.9 Relays Output
The control panel provides three relays rated for 2.0 amps @ 30 VDC (resistive) and 2.0 amps @ 30
VAC(resistive).
Relay connections may be power-limited or nonpower-limited, provided that a minimum of 0.25" is maintained
between conductors of power-limited and nonpower-limited circuits.
The ALARM RELAY is open in normal , it will be close in a any alarm.
The FAULT RELAY is open in normal, it will close in a any fault.
The SUPV. RELAY is open in normal , it will be close in INT1 or INT2 alarm.
2.10 Power-limited Wiring Requirements
Power-limited and nonpower-limited circuit wiring must remain separated in the cabinet. All power-limited
circuit wiring must remain at least 0.25" (6.35 mm) away from any nonpower-limited circuit wiring. Furthermore,
all power-limited and nonpower-limited circuit wiring must enter and exit the cabinet through different knockouts
and/or conduits. A typical wiring diagram for the PANEL is illustrated in Figure 2-3.
2.11 RS485 Communication with repeater panels
Page 27 of 36
A
B
+ 2 4 V -
R S 4 8 5
C o m m u n i c a t i o n
N o n R e s e t a b l e
D C 2 4 V P o w e r
F i r e A l a r m P a n e l
J P 1
A
B
+ 2 4 V -
R S 4 8 5
P O W E R
R e p e a t e r # 1
J P 1
A
B
+ 2 4 V -
R S 4 8 5
P O W E R
R e p e a t e r # 2
J P 1
A
B
+ 2 4 V -
R S 4 8 5
P O W E R
R e p e a t e r # 3 2
P o w e r S u p p ly W i r e s
R S 4 8 5 C o m m u n i c a i t o n W i r e s ( s h o u ld b e t w i s t e d s h i e l d w ir e s ) P o w e r S u p p ly W i r e s
Summary of Contents for HP101U
Page 6: ...Notes ...
Page 8: ...APPENDIX A BATTERY CALCULATIONS 27 APPENDIX B WIRE REQUIREMENTS 29 ...
Page 9: ...Main Circuit Board PANEL Terminals and Connectors Page 9 of 36 ...
Page 11: ...Page 11 of 36 ...
Page 12: ...The functions of terminal Page 12 of 36 ...
Page 13: ...Page 13 of 36 ...
Page 16: ...Page 16 of 36 ...
Page 17: ...FIGURE 1 3 2 PANEL 8 LEDs and Keypad Page 17 of 36 ...
Page 18: ...FIGURE 1 3 3 PANEL 16 LEDs and Keypad Page 18 of 36 ...
Page 24: ...Page 24 of 36 ...