Draw wires through the respective knockout locations.
FIGURE 2-2:
Cabinet Dimensions and Knockout Locations
2.3 Operating Power
WARNING:
Several different sources of power can be connected to this panel. Disconnect all sources of power
before servicing. The panel and associated equipment may be damaged by removing and/or inserting cards,
modules or interconnecting cables while this unit is energized.
Primary Power Source (AC) and Earth Ground Connections
AC power connections are made inside the control panel cabinet. The primary power source for the PANEL is
220 VAC, 50 Hz, 2.3 amps. Run a pair of wires (with ground conductor) from the protected premises main
breaker box to AC Power Terminal of the main circuit board. As per the Canadian Electrical Code, use 14 AWG
(2.00 mm
2
, 1.6 mm O.D.) or heavier gauge wire with 600V insulation. No other equipment may be connected to
this circuit. In addition, this circuit must be provided with overcurrent protection and may not contain any power
disconnect devices. A separate Earth Ground connection must be made to ensure proper panel operation and
lightning and transient protection. Connect the Earth Ground wire [minimum 14 AWG (2.00 mm
2
)] to the
mounting stud located on the cabinet.
Do not use conduit for the Earth Ground connection since this does not provide reliable protection.
Secondary Power Source (Batteries)
Observe polarity when connecting the battery. Connect the battery cable to Battery Terminal on the main circuit
board using the plug-in connector and cable provided. The battery charger is current-limited and capable of
recharging sealed lead acid type batteries. The charger shuts off when the system is in alarm. See “Battery
Page 22 of 36
Summary of Contents for HP101U
Page 6: ...Notes ...
Page 8: ...APPENDIX A BATTERY CALCULATIONS 27 APPENDIX B WIRE REQUIREMENTS 29 ...
Page 9: ...Main Circuit Board PANEL Terminals and Connectors Page 9 of 36 ...
Page 11: ...Page 11 of 36 ...
Page 12: ...The functions of terminal Page 12 of 36 ...
Page 13: ...Page 13 of 36 ...
Page 16: ...Page 16 of 36 ...
Page 17: ...FIGURE 1 3 2 PANEL 8 LEDs and Keypad Page 17 of 36 ...
Page 18: ...FIGURE 1 3 3 PANEL 16 LEDs and Keypad Page 18 of 36 ...
Page 24: ...Page 24 of 36 ...