3.5 Zone Disable
1. Press and held Mode key for more than three seconds until the Activate LED blinks.
2. Press “Up” and “Down” arrow key to select Zone Disable LED blinks.
3. Press “Enter (Mode)” key to enter Zone Disable menu.
3. Press “Up” and “Down” arrow key to select Zone1 to Zone16, the selected Zone LED blinks.
4. Press “Enter (Mode)” key to disable the corresponding zone. Then panel will be reset automatically.
5. After reset automatically, the disabled Zone Yellow LED turns on, and the Zone Disable LED turns on.
3.6 Sound Disable
1. Press and held Mode key for more than three seconds until the Activate LED blinks.
2. Press “Up” and “Down” arrow key to select Sound Disable LED blinks.
3. Press “Enter (Mode)” key to enter Sound Disable menu.
4. Press “Up” and “Down” arrow key to select Sound1 to 4, the selected Sound LED blinks.
5. Press “Enter (Mode)” key to disable the corresponding sound. Then panel will be reset automatically.
6. After reset automatically, the disabled Zone Yellow LED turns on, and the Zone Disable LED turns on.
3.7 Manual / Automatic running mode switch
1. Press and held Mode key for more than three seconds until the Activate LED blinks.
2. Press “Up” and “Down” arrow key to select Manual or Automatic LED blinks.
2. Press “Enter (Mode)” key to set panel running mode.
In program mode, press “Cancel (Silence”) key to exit the program mode in any time.
A pause of up to 30 seconds is allowed between each key press, otherwise the panel will exit program mode
anyway.
3.8 Zone Input mode selection
There is one jump J2 on the right bottom of main PCB board,
1. Short the terminal 1, 2, all zone input short circuit indicate the
fault event.
2. Short the terminal 2, 3, all zone input short circuit indicate the
alarm event.
3.9 Earth fault check selection
The panel could detect the power earth fault when
the Earth Check option is selected.
The J3 jump option on the PCB boatd is for you to select.
3.10 Earth fault check selection
The panel could detect the power earth fault.
Page 29 of 36
J 3
C H E C K E F
N O C H E C K E F
E A R T H F A U L T
C H E C K O P T I O N
Summary of Contents for HP101U
Page 6: ...Notes ...
Page 8: ...APPENDIX A BATTERY CALCULATIONS 27 APPENDIX B WIRE REQUIREMENTS 29 ...
Page 9: ...Main Circuit Board PANEL Terminals and Connectors Page 9 of 36 ...
Page 11: ...Page 11 of 36 ...
Page 12: ...The functions of terminal Page 12 of 36 ...
Page 13: ...Page 13 of 36 ...
Page 16: ...Page 16 of 36 ...
Page 17: ...FIGURE 1 3 2 PANEL 8 LEDs and Keypad Page 17 of 36 ...
Page 18: ...FIGURE 1 3 3 PANEL 16 LEDs and Keypad Page 18 of 36 ...
Page 24: ...Page 24 of 36 ...