Local Sounder
A piezo sounder provides separate and distinct sounds for alarm, trouble and supervisory conditions:
Alarm - pulse ½ second On and ½ second OFF
Fault - pulse 1½ second On and 4 second OFF
Supervisory - pulse ½ second On and ½ second OFF
1.4 Circuits
Input Circuits
Sixteen input circuits provide configuration. Input circuits 1 through 16 may be used as standard fire alarm
control panel zones. All sixteen Initiating Device Circuits accept normally-open contact devices and two-
wire smoke detectors.
Output Circuits
• 24 Volt Resettable Power Output 1000 mA
• 24 Volt Nonresettable Power Output 1000 mA
• 24 Volt Battery Charger (up to 18 AH batteries)
• EIA-485 Port (interfaces to Annunciators, and Graphic Annunciators and Remote Relay Module)
Sounder (Notification Appliance )Circuits
Four Notification Appliance Circuits.
Relays
Three dry relays for system alarm, system trouble and supervisory are provided standard. Contacts are rated
2.0 amps @ 30 VDC (resistive) and 2.0 amps @ 30 VAC (resistive).
EIA-485 Port
EIA-485 compatible port supports up to 32 repeater panels.
Battery Charger
Battery Charger will charge up to 18 AH batteries. The PANEL cabinet holds a maximum of 7 AH batteries.
The external box is required to hold 18 AH batteries. The charger is rated for 500 mA maximum current.
Page 19 of 36
Summary of Contents for HP101U
Page 6: ...Notes ...
Page 8: ...APPENDIX A BATTERY CALCULATIONS 27 APPENDIX B WIRE REQUIREMENTS 29 ...
Page 9: ...Main Circuit Board PANEL Terminals and Connectors Page 9 of 36 ...
Page 11: ...Page 11 of 36 ...
Page 12: ...The functions of terminal Page 12 of 36 ...
Page 13: ...Page 13 of 36 ...
Page 16: ...Page 16 of 36 ...
Page 17: ...FIGURE 1 3 2 PANEL 8 LEDs and Keypad Page 17 of 36 ...
Page 18: ...FIGURE 1 3 3 PANEL 16 LEDs and Keypad Page 18 of 36 ...
Page 24: ...Page 24 of 36 ...