2.4 Input Zones Circuits
The control panel has 4-16 zone input circuits. The maximum loop resistance limit for each input circuit is 100
ohms. All field wiring of each zone is supervised for opens and ground faults. Both conditions are visually and
audibly annunciated.
Each zone is a Initiating Device Circuit (IDC) designed to accept any normally-open contact devices and
conventional 2-wire, 24 volt smoke detectors.
All zones may be configured for general fire alarm applications.
Max 30 conventional detectors in one zone.
Four-wire smoke detectors may be connected to any zone. Resettable power is provided via RESETABEL DC24V
Terminal. Refer to the Device Compatibility Document for a list of compatible smoke detectors.
It is allowable to mix an assortment of device types (i.e. smoke detectors, heat detectors, pull stations, etc.) on any
zone.
2.5 Input Supervisory Appliance
Circuits
Any switch or push button can be connected in supervisory
terminal IN1, IN2.
Normal Close (NC) Alarm
: In the normal the switch that
connect to the IN1 and IN2 is closed, and the INT1 and INT2
has DC12V, when the switch open and the IN1 or IN2 without
DC12V, then there is a supervisory alarm.
Normal Open (NO) Alarm
: In the normal the switch that
connect to the IN1 and IN2 is opened, and the INT1 and INT2
has not DC12V, when the switch close and the IN1 or IN2 has
DC12V, then there is a supervisory alarm.
Page 25 of 36
J 1
N O A L A R M
N C A L A R M
Summary of Contents for HP101U
Page 6: ...Notes ...
Page 8: ...APPENDIX A BATTERY CALCULATIONS 27 APPENDIX B WIRE REQUIREMENTS 29 ...
Page 9: ...Main Circuit Board PANEL Terminals and Connectors Page 9 of 36 ...
Page 11: ...Page 11 of 36 ...
Page 12: ...The functions of terminal Page 12 of 36 ...
Page 13: ...Page 13 of 36 ...
Page 16: ...Page 16 of 36 ...
Page 17: ...FIGURE 1 3 2 PANEL 8 LEDs and Keypad Page 17 of 36 ...
Page 18: ...FIGURE 1 3 3 PANEL 16 LEDs and Keypad Page 18 of 36 ...
Page 24: ...Page 24 of 36 ...