CHAPTER 4
:
Operating Instructions
The PANEL has two modes of operation which are Normal, Program.
Upon initial power-up, the system will be in Normal Mode. This section discusses operation of the control panel
in the
Normal Mode.
4.1 Switch Functions in Normal Mode
Silence
A Silence key is located on the PANEL keypad (illustrated in Figure 4-1).
If Silence keys is pressed, the following will occur:
✓
The silenceable Notification Appliance Circuits (Sound1-Sound 4 Output) will be turned OFF.
✓
The corresponding Sound LED will be turned OFF
✓
The main circuit board signal Silence LED will be turned ON
Upon the occurrence of a subsequent event (alarm or trouble), signal Silence is overridden and the control
panel will respond to the new event.
Mute
An Mute key is located on the PANEL keypad (refer to Figure 4-1), The Mute key silences the system piezo
sounders and changes all flashing system LEDs to steady. Pressing the Mute key will have no effect on the
Notification Appliance Circuits.
Test
If the Test key is pressed, the PANEL will perform a Lamp Test, All panel LEDs will be turned on and the
piezo will sound.
Reset
Page 30 of 36
Summary of Contents for HP101U
Page 6: ...Notes ...
Page 8: ...APPENDIX A BATTERY CALCULATIONS 27 APPENDIX B WIRE REQUIREMENTS 29 ...
Page 9: ...Main Circuit Board PANEL Terminals and Connectors Page 9 of 36 ...
Page 11: ...Page 11 of 36 ...
Page 12: ...The functions of terminal Page 12 of 36 ...
Page 13: ...Page 13 of 36 ...
Page 16: ...Page 16 of 36 ...
Page 17: ...FIGURE 1 3 2 PANEL 8 LEDs and Keypad Page 17 of 36 ...
Page 18: ...FIGURE 1 3 3 PANEL 16 LEDs and Keypad Page 18 of 36 ...
Page 24: ...Page 24 of 36 ...