Appendix A
Battery Calculations
Use the Total Standby and Alarm Load Currents calculated in Table A-2 and Table A-3 for the following battery
calculation.
TABLE A-1: Battery Calculation
Standby Load Required Standby Time in Hours
Current (amps) X (24 or 60 Hours) =
[ ] [ ]
Alarm Load Required Alarm Time in Hours
Current (amps) X (i.e. 5 min. = 0.084 hours) =
[ ] [ ]
Add Standby and Alarm Load for Required Ampere Hour Battery =
Multiply by derating factor of 1.2 X1.2
Note:
1. 7 Ampere Hour battery can be located in the backbox.
2. Batteries larger than 7 Ampere Hour, up to 18 Ampere Hour, require the External battery box.