Instruction for installation and operation 

 

 

Of Manual call point 

 

D9000 МСР

 

 

 

 

 

Atention: Read this instruction carefully before attempting to install the detector. 

 

The  D9000  MCP  manual  call  point  is  designed  for  indoor  operation  in  fire  detection  systems  and  meets  the 

requirements of European Standard EN54-11; 

 The fire detector is designed for easy installation and maintenance. There are built-in channels in the base for 

inserting cables in three directions  - left, right, and top. The key to open the fire detector and restore the  removed 
element is the same and is attached to the base. D9000 The MCP has a protective transparent cover and a possibility 
of  mounting  a  seal.  Upon  activation,  except  the  graphic  indication  of  the  operating  element,  for  visibility  from  a 
distance is activated and red LED. 

1. 

Technical characteristics  

-

 

Supply voltage 

 

  

 

 

(9-30) V DC 

-

 

Resistance   

 

 

 

 

500Ω / (1 kΩ in broken PCB bridge)   

 

Current at 24V 

 

 

 

 

46mA/ (22mA in broken PCB bridge) 

 

LED indicator  

 

 

 

 

red 

 

Protective cover    

 

 

 

transparent  

 

Cross section of connecting cables 

 

0,4÷1,5 mm2 

 

operating temperature range 

 

 

minus 10ºС ÷ 50ºС 

 

Humidity   

 

 

 

 

(93 ± 3)% at 40ºС 

 

Degree of protection 

 

 

 

IP 40 

 

Dimensions 

 

 

 

 

(90 х 90 х 44) mm 

 

Weight 

 

 

 

 

 

0,120 kg 

 

Material   

 

 

 

 

ABS plastic 

 

2.

 

Installation of the fire detector 

-

 

Unpack the fire detector;

 

-

 

Remove the key from the base.   

 

-

 

Insert the key in the base opening, push inward and open the two parts of the fire detector.

 

-

 

 Select the location (according to the project drawings) for installation of the fire detector;

 

-

 

Install the base with suitable dowels and screws;

 

-

 

Connect the electric cables according to the diagram (fig.1)

 

-

 

In the factory fire detector is designed to switch 500Ω resistor or current in the line 46mA / at 24V DC; 

-

 

It is possible to set the resistance, which can be set to 1 k Ω or current in the line 22mA / at 24V DC 


 
 